Fire Risk Assessment in High-Rise Hopitalls in Accordance With NFPA 101

Evaluación de riesgo de incendio en Hopitalls de gran altura de acuerdo con NFPA 101

Abdolrasoul Rahmani
Department of Occupational Health Engineering, School of Health, Shiraz University of Medical Sciences, Shiraz, Iran, Irán
Mohammad Salem
Department of Occupational Health Engineering, School of Health, Baqiyatallah University of Medical Sciences, Tehran, Iran, Irán

Fire Risk Assessment in High-Rise Hopitalls in Accordance With NFPA 101

Revista Latinoamericana de Hipertensión, vol. 13, no. 3, pp. 242-245, 2018

Sociedad Latinoamericana de Hipertensión

Derechos reservados. Queda prohibida la reproducción total o parcial de todo el material contenido en la revista sin el consentimiento por escrito del editor en jefe. Copias de los artículos: Todo pedido de separatas deberá ser gestionado directamente con el editor en jefe, quien gestionará dicha solicitud ante la editorial encargada de la publicación.

Abstract: Protection the high-rise hospitals against fire is very important due to presence of disable patients, hospital’s diverse population, multiple floors and having multiple units on floors. The present study was aimed to assess fire risk in a high-rise hospital. Assessment NFPA healthcare worksheets were extracted from NFPA101 standard completed through field observation. In the next stage, gathered information was analyzed using CFSES software. From all studied zones 100% in the aspects of fire containment and extinguishment were unacceptable. In total, the fire risk level was acceptable in 80% and 100% in the aspects of people movement and general safety, respectively. Our findings indicated that to improve the level of fire risk in high rise hospitals, required measures especially in the area of fire extinguishment and containment including buildings design for automatic sprinkler systems and standardization of fire controls.

Keywords: High-rise hospitals, Fire risk assessment, NFPA 101, CFSES software.

Resumen: La protección de los hospitales de gran altura contra el fuego es muy importante debido a la presencia de pacientes discapacitados, la población diversa del hospital, pisos múltiples y tener varias unidades en el piso. El presente estudio tuvo como objetivo evaluar el riesgo de incendio en un hospital de gran altura. Evaluación Las hojas de trabajo de salud de la NFPA se extrajeron del estándar NFPA101 completado a través de la observación de campo. En la siguiente etapa, la información reunida se analizó utilizando el software CFSES. De todas las zonas estudiadas, el 100% en los aspectos de contención y extinción de incendios fueron inaceptables. En total, el nivel de riesgo de incendio fue aceptable en 80% y 100% en los aspectos de movimiento de personas y seguridad general, respectivamente. Nuestros hallazgos indicaron que para mejorar el nivel de riesgo de incendio en hospitales de gran altura, se requieren medidas especialmente en el área de extinción de incendios y contención, incluido el diseño de edificios para sistemas de rociadores automáticos y la estandarización de los controles de incendios.

Palabras clave: Hospitales de gran altura, evaluación de riesgo de incendio, NFPA 101, software CFSES.

Introduction

Hospitals are in the business of preserving and restoring health and comfort. At the same time, they must protect their patients and staff from fire and other hazards. Protection the hospitals against fire is very important due to presence of disable persons, lack of awareness and expensive devices and equipments in the hospitals (Jahangiri et al., 2016). In 2011-2015, National Fire Protection Association (NFPA) responded to an estimated annual average of 5,750 structure fires in health care properties each year. These fires caused annual averages of two civilian deaths, 157 civilian injuries, and $50.4 billion in direct property damage (Richard, 2017).

Fire safety is one of the greatest challenges facing the designers and operators of high-rise hospitals. This is particularly true where patients are highly dependent on members of staff, for example, the elderly, the mentally ill, those in intensive care units, etc (Koohpaie et al., 2011). In an emergency evacuation situation in a high-rise hospital, many patients will be unable to walk independently out of the hospital (Charters, 1996). Because high-rise hospitals tend to have more patients and a longer distance to the exit discharge, fire prevention and fire risk assessment for building are essential.

The aim of high-rise hospital fire risk analysis is to gain insight into and characterize fire-related risks to better inform the wide range of decisions that must be made as part of hospital design, construction, and operation (Meacham et al., 2016). Therefore, the results from this study can potentially help in furtherance of research in a particular field of knowledge and can be a guidance in administering the workplace health and safety promotion program.

Materials and Methods

This cross-sectional descriptive study was conducted in a high-rise hospital (12 floor) in accordance with life safety code of NFPA, also known as NFPA 101. The goal of this code is fire risk assessment to provide an environment for the occupants that is reasonably safe from fire and similar emergencies. Items listed in NFPA 101 healthcare worksheets included occupancy risk parameters (patient mobility, mobility status factor, zone location, ratio of patients to attendants, patient average age) and fire safety (construction, manual fire alarm, smoke detection and alarm, automatic sprinklers, interior finish, door to corridor, zone dimension, emergency movement routes, corridor partitions/ walls and vertical opening) and completed through field observation (NFPA, 2013). In the next stage, gathered information was analyzed using Computerized Fire Safety Evaluation System (CFSES) software. This method was developed based on the NFPA101 standard and evaluates the fire risk from four dimensions of containment, extinguishment, people movement and general safety.

Results: The descriptive information on occupancy risk and fire safety parameter of the studied high-rise hospital was presented in Table 1 and 2.

Table 1
Descriptive information on occupancy risk parameters of the studied hospital
ParametersStatusNumber of ZonesPercent (%)
Patient MobilityMobile1136.6
Limited Mobility1240
Not Mobile310
Not Movable413.4
Mobility Status Factor1-5310
6-101343.2
11-301033.4
>30413.4
Zone Location1st26.6
2nd or 3rd723.4
4th to 6th723.4
7th and above1446.6
Ratio of Patients to Attendants1-2∕1826.7
3-5∕11756.6
6-10∕113.3
>10∕1413.3
Patient Average Age<65 Years and > 1 Year2790
≥65 Years or ≤1 Year310

Table 2
Descriptive information on fire safety parameters of the studied hospital
ParametersStatusNumber of ZonesPercent (%)
ConstructionFirst and Non-Combustible26.6
Second and Non-combustible413.3
Third and Non-combustible26.6
4th and Above and Non-combustible2273.5
Manual Fire AlarmManual Fire Alarm30100
No Manual Fire Alarm00
Smoke Detection and AlarmNone00
Corridor Only00
Rooms Only00
Corridor and Habit Spaces00
Total Space in Zone30100
Automatic SprinklersNone2790
Corridor and Habit Spaces00
Entire Building310
Interior Finish (corridors and exits)Class A30100
Class B00
Class C00
Interior Finish(rooms)Class A30100
Class B00
Class C00
Door to CorridorNo Door00
< 20 Min FPR00
≥ 20 Min FPR00
≥ 20 Min FPR and Auto clos30100
Zone DimensionDead End620
No Dead Ends> 30 ft2480
Emergency movement routes< 2 Route826.6
Multiple Route2273.4
Corridor Partitions/ WallsNone or Incomplete00
< ⅟2 hr00
≥⅟2 hr to < 1 hr30100
≥1 hr00
Vertical OpeningOpen 4 or More Floors00
Open 2 or 3 Floors00
Enclosed with Indicated Fire Resist30100
Note: The list of abbreviations, FPR: Fire Protection Rating

The final results of fire risk assessment are presented in Fig 1. As can be seen, fire risk from containment and extinguishment dimensions is unacceptable in all of the zones under investigation. Fire risk from the dimension of people movement is unacceptable in 6 (20%) zones. The current study found that fire risk from the general fire safety dimension is acceptable in 30 (100%) of the studied zones and is best in four dimensions.

Fire risk assessment from all four dimension
Fig 1.
Fire risk assessment from all four dimension

Discussion

The principal objective of this study was to establish the fire risk assessment in high-rise hospital accordance with NFPA 101 in order to support human health risk assessment. Considering the above assumption, the most finding of the study is that from all studied zones 100% in the aspect of containment, 100% in the aspect of extinguishment and 20% in the aspect of people movement were unacceptable. In total, the fire risk level was acceptable only in general safety aspect (100%) of the studied zones.

A fundamental knowledge of fire containment and extinguishment necessary to make reasonable judgments about action priorities and viable egress routes (NFPA, 2013). In the study reported here, the level of fire extinguishment and containment were lower compared to the prescribed by the life safety code. It was important to identify special considerations for high-rise hospital building to prevent parallel mistakes and problems which may be encountered. These lessons should be used to manage existing hospital buildings and the design of new high-rise hospital. Most researchers, such as Wei-Wen et al.2011 and Taaffe et al. 2005, agreed that there are special considerations for fire safety in high-rise hospital buildings compared to other buildings. Considerations include the long route to exit, patient incapable of self-evacuating, flammable matter and chemicals.

It was discovered that the main cause of high casualties in the hospital fire accidents which happened before 1950 was the lack of installation of automatic fire systems. They provide a longer period for the public to emerge from the high-rise hospitals (Ong and Suleiman, 2015). Very often the structures involved could be saved if an automatic sensoring system, together with a nearby supply of water were available to wet the structure down in sufficient time to prevent the structure from being set afire by small localized fires (Gelaude et al., 1984). Automatic sprinkler systems add several benefits to high-rise hospitals as the system has a high probability of extinguishing or controlling the fire and detect fire at an early stage. In other words, these automated systems alert the public once they detect the fire source (Ong and Suleiman, 2015). Statistics states that the system is able to operate effectively in 90-95 % of all fires large enough to serve a potential threat to the hospital and its occupants (Nystedt, 2010).

Also, evidence-based results show that each opening was protected by an approved self-closing fire door that remains closed or automatically closed in an emergency. Vents, stairways, and elevator channel, allowing smoke to move throughout the high-rise buildings in just minutes. In a high-rise hospital, patients and occupants on upper floors can quickly become trapped by smoke and flames, particularly if the elevators and stairwells are filled with smoke. Smoke often travels a long distance from the fire floor (Black, 2009). Some research on smoke propagation has been developed. Air curtain could be utilized for confinement of fire-induced smoke and carbon monoxide transportation along channels (Hu et al., 2008). Comparison results between louver system and chimney system show that the chimney system provides a more stable smoke and temperature stratification inside the building and a higher hot smoke layer above the floor (Chen and Yung, 2007).

Besides that, researchers also studied the occupant’s safe egress and people movement. Based on these results, fire risk from the dimension of people movement is acceptable in 24 (80%) zones. Evacuation is the process in which the occupants in a hospital building notice a fire and whereupon they experience several mental processes and carry out several actions before and/or during the movement to a safe place in or outside the building (SFPE, 2002). Evacuation time of patients and staff often draws major attention because of the hospital’s diverse population, mix of patient conditions, multiple floors, and having multiple units on one floor. A hospital is a special facility for providing medical services to its patients. It includes a numerous type of wards, such as general wards, intensive care unit (ICU), psychiatric unit and so on (Huang. 2003). At least two exit routes must be available in a floor of high-rise hospitals to permit prompt evacuation of patients and other hospital occupants. The capacity of an egress route must be adequate and must support the maximum permitted occupant load for each floor served and must lead directly outside or to a street, walkway, refuge area, public way, or open space with access to the outside (NFPA, 2013).

In general, during fire related events or emergencies, high-rise hospitals must remain safe, accessible and functioning at maximum capacity in order to help save lives. Making hospitals safe involves knowledge of the many factors that contribute to their vulnerability during an emergency such as the building’s location, design specifications, materials used, fire containment and extinguishment and interior finish contribute to the ability of the hospital to withstand adverse natural events.

Conclusions

Our findings indicated that to improve the level of fire risk in high rise hospital, required measures especially in the area of fire extinguishment and containment including buildings design for automatic sprinkler systems and standardization of fire controls.

Agradecimientos

This study was supported by Baqiyatallah University of Medical Sciences (Grant no. 96-07-001732). We would also like to thank from the Clinical Research Development Center of Baqiyatallah Hospital for their kindly cooperation.

References

1. Black, W. Z (2009). Smoke movement in elevator shafts during a high-rise structural fire. Fire Safety Journal, 44(2), pp. 168-182.

2. Charters, D.A (1996). Quantified assessment of hospital fire risks. InProc. Interflam. 96, pp. 641-651.

3. Chen, Z. D., & Yung, D (2007). Numerical study of two air intake strategies for a new fire laboratory. Journal of Fire Protection Engineering, 17(1), 27-40.

4. Gelaude, J. L (1984). U.S. Patent. Washington, DC: U.S. Patent and Trademark Office. 4, pp. 428,434.

5. Hu, L. H., Zhou, J. W., Huo, R., Peng, W., & Wang, H. B (2008). Confinement of fire-induced smoke and carbon monoxide transportation by air curtain in channels. Journal of hazardous materials, 156(1-3), pp. 327-334.

6. Huang, Y.H (2003). A study on the influential factors of the fire protection for hospital wards, Master’s thesis, Central Police University (In Chinese).

7. Jahangiri, M. E. H. D. I., Rajabi, F. A. Z. E. L., & Darooghe, F. A. H. I. M. E (2016). Fire risk assessment in the selected Hospitals of Shiraz University of Medical Sciences in accordance with NFPA101. Iran Occupational Health, 13(1), pp. 99-106.

8. Koohpaie, A. R., Jafari, M. J., Yarahmadi, R., Mahdinia, M., & Khazaei, M (2011). Fire risk assessment and the effect of emergency planning on risk reduction in a hospital. Majallah-i Dānishgāh-i ̒Ulūm-i Pizishkī-i Qum, 5(3), pp. 71-78.

9. Meacham, B. J., Charters, D., Johnson, P., & Salisbury, M (2016). Building fire risk analysis. In SFPE Handbook of Fire Protection Engineering. Springer, New York, NY. pp. 2941-2991.

10. National Fire Protection Association. (2013). NFPA 101A, Guide on Alternative Approaches to Life Safety. National Fire Protection Association.

11. Nystedt, F (2010). Verifying fire safety design in sprinklered buildings. Department of Fire Safety Engineering and Systems Safety, Lund University.

12. Ong, W.C., Suleiman, Z (2015). Fire safety management problems in fire accidents in hospital building. Advances in Environmental Biology. 1, pp. 43-7.

13. Richard, C (2017). Fires in health care facilities.

14. SFPE. (2002). Society of Fire Protection Engineers, Engineering Guide to Human Behaviour in Fire: Review Draft.

15. Taaffe, K.M., Kohl, R., Kimbler, D.L (2005). Hospital evacuation: issues and complexities. InProceedings of the 37th conference on winter simulation. Winter Simulation Conference. pp. 943-950.

16. Wei-Wen, T., Kuo-Hsiung, P., & Che-Ming, H (2011). Performance-based fire safety design for existing small-scale hospitals. Procedia Engineering, 11, pp. 514-521.